Mon Nov 12 07:40:34 EST 2007 Input file [ heatxchngr.txt ] #----------------------Input---------------------# mdothot 1.0 (kg / s) Cphot 2200 (J / kg / K) Thotin 100 (deg C) Thotout 50 (deg C) mdotcool 2.0 (kg / s) Cpcool 4200 (J / kg / K) Tcoolin 25 (deg C) Tcoolout 38 (deg C) Type 2 (1 = parallel; 2 = counterflow) #-----------------Output--------------------# Qhot= -110000 Watts Qcool= 109200 Watts Qhot+Qcool must = zero or following calcs are wrong Counter-flow x-chngr, Thotout must be > Tcoolin Overall U is the overall heat transfer coefficient of the design (W/m^2/C). A is the effective heat transfer area of the design (m^2). UA and Qcheck shown below is based on coolside flow. LMTD = 40.74 C Overall U * Area = 2680.59 Watts/C Qcheck = 109200.00 Watts #.......................End of File..............#